Description
Non-powered, positive-action valves designed to intercept the flow of fuel to the burner to prevent the temperature of the water in the system's delivery circuit from reaching the burner temperature.
Since the VIC is a positive action valve, to close it you can act by: drilling or cutting the capillary and/or the sensor bulb (since they are positive action valves, in this case it is not possible to reset the valve) or by raising the water temperature until it reaches the calibration point of 98°C (+ 0 - 5°C) (in this case it is possible to reset the valve only if the temperature drops to at least 87°C ± 2°C)
INAIL APPROVED
Datasheet
• Use of gas from the 3 families, diesel and fuel oil
• Calibration temperature 98°C (+ 0 - 5°C)
• Maximum operating pressure 1 bar
• Operating temperature - 15°C ÷ + 70°C
• Capillary length 5 m
• Mechanical resistance group 2 (according to EN 13611:2007)
• NBR and Viton FKM rubber seals (UNI ISO 4658)
• G 1/2" well connection