Description
Solution for security, intrusion, smoke and fire detection systems with a mixed conductor configuration that combines two larger 0.75 mm² conductors and six smaller 0.22 mm² conductors.
All conductors are made of copper with flame-retardant PVC insulation, while the white PVC outer sheath offers strength and ease of installation.
The cable is certified with fire reaction class Cca‑s3,d1,a3, according to the CPR EN 50575 standard, and is designed for fixed installation.
It is suitable for signal transmission and control applications in alarm systems, but is not suitable as a power cable.
It can coexist with power cables up to 450/750 V and 0.6/1 kV without interference.
Datasheet
• 2x0.75 mm² + 6x0.22 mm² copper conductors
• Flame-retardant PVC insulation
• Conductor color red, black, DIN 47100
• White flame-retardant PVC outer sheath
• Outer sheath diameter approximately 5.1 mm
• Mutual capacitance of the cable approximately 120 pF/m
• Insulation resistance ≥ 200 GΩ km (20 °C)
• Operating temperature ‑10 °C / +80 °C
• CPR fire reaction class Cca‑s3,d1,a3
• Application in alarm systems, intrusion detection, smoke and fire detection, industrial monitoring
• Fixed installation (not as a power cable)
• Suitable for cohabitation with 450/750 V and 0.6/1 kV power cables